K8DT-VS

Features

Single-phase voltage relay

Detect abnormal voltages applies to equipment to protect against equipment failure. Use in either overvoltage or undervoltage mode.

  • Monitor AC or DC voltages with one relay
  • Settings for the operating value, hysteresis, and operating time
  • Width of 17.5 mm to reduce space required in panels
  • Push-in plus Technology that reduce wiring work
  • UL listed for easy shipping to North America
  • Double-insertion holes for crossover wiring (all terminals)
  • Models added with transistor outputs for superior contact reliability
  • RoHS compliant
Specifications & ordering info

Ordering information

Setting range

Power supply voltage

Output

Order code

1 to 10 V AC/DC

3 to 30 V AC/DC

15 to 150 V AC/DC

24 VAC/DC

Relay: SPDT contact output

K8DT-VS2CD

Transistor: Open collector

K8DT-VS2TD

100 to 240 VAC

Relay: SPDT contact output

K8DT-VS2CA

Transistor: Open collector

K8DT-VS2TA

20 to 200 V AC/DC

30 to 300 V AC/DC

60 to 600 V AC/DC

24 VAC/DC

Relay: SPDT contact output

K8DT-VS3CD

Transistor: Open collector

K8DT-VS3TD

100 to 240 VAC

Relay: SPDT contact output

K8DT-VS3CA

Transistor: Open collector

K8DT-VS3TA

Accessories

Front Cover (Order separately)

Appearance

Order code

 

Y92A-D1A

Specifications

Item

K8DT-VS2

K8DT-VS3

Power supply voltage

K8DT-VS__D

24 VAC 50/60 Hz, 24 VDC

K8DT-VS__A

100 to 240 VAC 50/60 Hz

Power consumption

24 VAC/DC: 1.8 VA/1 W max.

100 to 240 VAC: 2.5 VA max.

Operate (SV)

Operating value setting range

10% to 100% of the maximum value of the setting range

1 to 10 VAC/DC

3 to 30 VAC/DC

15 to 150 VAC/DC

10% to 100% of the maximum value of the setting range

20 to 200 VAC/DC

30 to 300 VAC/DC

60 to 600 VAC/DC

Operating value

100% operation at set value

Reset (HYS)

Reset value

5% to 50% of operating value

Resetting method

Manual reset/automatic reset (switchable)

Operating time setting range (T)

0.1 to 30 s

Power ON lock time

1 s or 5 s (Switched using DIP switch.)

Indicators

Power (PWR): Green, Relay output (RY): Yellow, Alarm outputs (ALM): Red

Output form

Relay: SPDT contact output

Transistor: Open collector

Switchable between normally open and normally closed with a DIP switch setting.

Output relays ratings

Resistive load

5 A at 250 VAC

5 A at 30 VDC

Inductive load

1 A at 250 VAC

0.2 A at 48 VDC

Minimum load

5 VDC, 10 mA (reference values)

Mechanical life

10 million operations min.

Electrical life

5 A at 250 VAC or 30 VDC: 50,000 operations

3 A at 250 VAC or 30 VDC:100,000 operation

Transistor output ratings

Contact form

SPST-NO (Open collector)

Rated voltage

24 VDC (maximum voltage: 26.4 VDC)

Maximum current

50 mA DC

Ambient operating temperature

-20 to 60°C (with no condensation or icing)

Storage temperature

-25 to 65°C (with no condensation or icing)

Case material

PC, UL 94 V-0

Weight

Approx. 100 g

Size in mm (H × W × D)

90×17.5×90

Operating voltage range

85% to 110% of power supply voltage

Rated power supply frequency

50/60 Hz ±5 Hz

Input frequency range

40 to 500 Hz

Overload capacity

Continuous input at 115% of maximum input, 10 s at 125% (up to 600 VAC)

Repeat error

Operating value

±0.5% full scale (at 25°C and 65% humidity, rated power supply voltage)

Operating time

±50 ms (at 25°C and 65% humidity, rated power supply voltage)

Applicable standards

Conforming standards

EN 60947-5-1

Installation environment (pollution level 2, Overvoltage category III)

EMC

EN 60947-5-1

Safety standards

UL 60947-5-1 (Listing), Korean Radio Waves Act (Act 10564), CCC (GB14048.5)

Degree of protection

Terminals: IP20

Have a question?

We are ready to help.

Contact us

Subscribe to product updates

Newsletters about product innovations, solutions and services, directly in your inbox.

Thank you for subscribing to Omron's eNews. You will shortly receive an e-mail from us. This e-mail contains a link which activates your email newsletter subscription. This method is used due to legal issues and to make certain that no-one can abuse your e-mail address.

We are experiencing technical difficulties. Your form submission has not been successful. Please accept our apologies and try again later. Details: [details]

Download

Product documentation

Download datasheets, manuals and brochures.

Browse download center

Training courses

Get the training from our best engineers. Beginner to advanced level.

View training courses