K8DS-PZ

Features

Slim-line three-phase voltage, asymmetry and phase-sequence phase-loss protection

K8DS-PZ monitors undervoltages, overvoltages, voltage asymmetry, phase sequence and phase loss for 3-phases, 3-wire monitoring in one unit.

  • Worldwide power specifications supported by one unit
  • Front rotary switches allow for easy and accurate configuration
  • Reset method: automatic
  • LED indicators: Power (Green), Relay output (Yellow), Alarm output (Red)
  • Robust operating temperature: -20 to 60 ⁰C
  • 17.5 mm (w) body
  • Greater resistance to inverter noise
  • World-wide power specifications supported by one unit
Specifications & ordering info

Ordering information

Rated input

Order code

3-phase 3-wire mode

200, 220, 230, 240 VAC

K8DS-PZ1

3-phase 3-wire mode

380, 400, 415, 480 VAC

K8DS-PZ2

Specifications

Ambient operating temperature

-20 to 60°C (with no condensation or icing)

Storage temperature

-25 to 65°C (with no condensation or icing)

Altitude

2,000 m max.

Input frequency

50/60 Hz (AC power supply)

Output relays
(1 × SPDT, normally closed operation)

Resistive load

5 A at 250 VAC or at 30 VDC

Maximum contact voltage

250 VAC or 30 VDC

Maximum contact current

5 A

Maximum switching capacity

1,250 VA, 150 W

Mechanical life

10,000,000 operations

Electrical life

50,000 operations at 5 A, 250 VAC

Degree of protection

Terminal section: IP20

Case material

PC UL94 V-0

Weight

Approx. 65 g

Rated input voltage

K8DS-PZ1

3-phase, 3-wire mode: 200, 220, 230, 240 VAC

K8DS-PZ2

3-phase, 3-wire mode: 380, 400, 415, 480 VAC

Operation (overvoltage or undervoltage)

Operating value setting range

Overvoltage/undervoltage: 2% to 30% of rated input voltage

Operating value

100% operation at set value

Asymmetry operation (ASY.)

Operating value setting range

Asymmetry rate: 5% to 22%

Operating value

100% operation at set value

Asymmetry operating value = rated input voltage x asymmetry set value [%]

The asymmetry operation will function when the difference between the highest and lowest voltage phases equals or exceeds the asymmetry operating value

Reset (HYS.)

Hysteresis

5% of operating value (fixed)

Resetting method

Automatic reset

Operating time (T)

Asymmetry

0.1 to 30 s

Overvoltage/undervoltage

0.1 to 30 s

Phase-sequence, phase-loss

0.1 s ±0.05 s, 0.1 s max.

Power ON lock (LOCK)

1 s ±0.5 s

Overload capacity

Continuous input: 500 V

Repeat accuracy

Operating value

±0.5% full scale (at 25°C and an ambient humidity of 65% at the rated power supply voltage, 50/60 Hz sine wave input)

Operating time

±50 ms (at 25°C and 65% humidity, rated power supply voltage)

Indicators

Power (PWR): Green, Relay output (RY): Yellow LED, Alarm output: Red LED

Applicable standards

Conforming standards

EN 60947-5-1
Installation environment (pollution level 2, installation category III)

EMC

EN 60947-5-1

Safety standards

UL 508 (Recognition), Korean Radio Waves Act (Act 10564), CSA: C22.2 No.14

Size in mm (H × W × D)

80 × 17.5 × 74

Have a question?

We are ready to help.

Contact us

Subscribe to product updates

Newsletters about product innovations, solutions and services, directly in your inbox.

Thank you for subscribing to Omron's eNews. You will shortly receive an e-mail from us. This e-mail contains a link which activates your email newsletter subscription. This method is used due to legal issues and to make certain that no-one can abuse your e-mail address.

We are experiencing technical difficulties. Your form submission has not been successful. Please accept our apologies and try again later. Details: [details]

Download

Product documentation

Download datasheets, manuals and brochures.

Browse download center

Training courses

Get the training from our best engineers. Beginner to advanced level.

View training courses