G3PE

Features

Omron’s G3PE Compact Industrial SSR with outstanding surge endurance

The G3PE features an original surge-pass circuit that gives outstanding surge endurance and protects the semiconductor device against voltages in excess of 30kV.

  • Single and three phase, 15-45 A output current
  • 100-240VAC and 200-480 VAC output voltages
  • Models available without zero cross
  • Improved surge dielectric strength for output circuits
  • Terminal cover with finger protection
  • Mount to DIN track or with screws
Specifications & ordering info

Ordering information

Phases

Rated voltage
(operating voltage)

Rated output load

Permissible I2t
(half 60 Hz wave)

Applicable heater capacity
AC1: resistive load)

Size in mm (H×W×D)

Number of poles

Order code

1

100 to 240 VAC
(75 to 264 VAC)

15 A (at 40°C)

121 A 2 s

3 kW (at 200 VAC)

100×22.5×100

1

G3PE-215B DC12-24

25 A (at 40°C)

260 A 2 s

5 kW (at 200 VAC)

1

G3PE-225B DC12-24

35 A

1,260 A 2 s

7 kW (at 200 VAC)

100×44.5×100

1

G3PE-235B DC12-24

45 A

9 kW (at 200 VAC)

1

G3PE-245B DC12-24

200 to 480 VAC
(180 to 528 VAC)

15 A (at 40°C)

128 A 2 s

6 kW (at 400 VAC)

100×22.5×100

1

G3PE-515B DC12-24

25 A (at 40°C)

1,350 A 2 s

10 kW (at 400 VAC)

1

G3PE-525B DC12-24

35 A

14 kW (at 400 VAC)

100×44.5×100

1

G3PE-535B DC12-24

45 A

6,600 A 2 s

18 kW (at 400 VAC)

1

G3PE-545B DC12-24

3

200 to 480 VAC
(180 to 528 VAC)

15 A (at 40°C)

260 A 2 s

12.5 kW (at 480 VAC)

100×80×155

3

G3PE-515B-3N DC12-24

2

G3PE-515B-2N DC12-24

25 A (at 40°C)

20.7 kW (at 480 VAC)

120×80×155

3

G3PE-525B-3N DC12-24

100×80×155

2

G3PE-525B-2N DC12-24

35 A

1,260 A 2 s

29 kW (at 480 VAC)

140×80×155

3

G3PE-535B-3N DC12-24

120×80×155

2

G3PE-535B-2N DC12-24

45 A

37.4 kW (at 480 VAC)

140×110×155

3

G3PE-545B-3N DC12-24

140×80×155

2

G3PE-545B-2N DC12-24

Specifications

Rated input voltage

12 to 24 VDC

Operating voltage range

9.6 to 30 VDC

Rated input current (impedance)

7 mA max. (zero cross models); 15 mA max. (models without zero cross)

Zero cross function

Yes

Must operate voltage

9.6 VDC max.

Must release voltage

1 VDC min.

Isolation method

Phototriac coupler

Operation indicator

Yes (yellow)

Load voltage range

200 to 480 VAC models: 180 to 528 VAC

100 to 240 VAC models: 75 to 264 VAC

Operate time

1/2 of load power source cycle +1 ms max.

Release time

1/2 of load power source cycle +1 ms max.

Leakage current

10 mA (at 200 VAC)

Ambient temperature

Operating: -30 to 80°C

Have a question?

We are ready to help.

Contact us

Subscribe to product updates

Newsletters about product innovations, solutions and services, directly in your inbox.

Thank you for subscribing to Omron's eNews. You will shortly receive an e-mail from us. This e-mail contains a link which activates your email newsletter subscription. This method is used due to legal issues and to make certain that no-one can abuse your e-mail address.

We are experiencing technical difficulties. Your form submission has not been successful. Please accept our apologies and try again later. Details: [details]

Download

Product documentation

Download datasheets, manuals and brochures.

Browse download center

Training courses

Get the training from our best engineers. Beginner to advanced level.

View training courses